INTU FR COLLAR (ST)
Intumescent pipe collar
Product description
The INTU FR COLLAR (ST) consists of one or more layers of graphite-based intumescent inserts, each with a nominal thickness of 2.0 mm, enclosed in a stainless steel housing. The collar is equipped with a locking clasp to secure its ends and keep it stable on the pipe, along with mounting brackets for fixing it to the wall or floor.
The INTU FR COLLAR is available in a red housing version – INTU FR COLLAR – and in a stainless steel housing version – INTU FR COLLAR (ST). Both collars are the same product with very high fire protection parameters – in a fire, the collar creates a barrier, ensuring the partition maintains its tightness and insulation up to EI 240.
-
Fire resistance class up to EI 240
-
Combustible pipes fire protection
-
For walls and floors
-
Quick installation
-
High degree of swelling
-
Certification LEED & BREEAM
Documents
Compliance
- European Technical Assessment: ETA-19/0844
- Declaration of Performance: DoP 2/2019
- Certificate of Constancy of Performance: 1488-CPR-0825/W
- VOC Emission test report – Indoor Air Comfort GOLD
- Certification LEED & BREEAM
Availability
| Product | Type | Delivery form | Article number | Delivery group |
| INTU FR COLLAR (ST) | 32 mm | 1 pc | 1503230042 | A |
| 40 mm | 1 pc | 1504030042 | A | |
| 55 mm | 1 pc | 1505530062 | A | |
| 63 mm | 1 pc | 1506330062 | A | |
| 75 mm | 1 pc | 1507530062 | A | |
| 82 mm | 1 pc | 1508230082 | A | |
| 90 mm | 1 pc | 1509030082 | A | |
| 110 mm | 1 pc | 1511030102 | A | |
| 125 mm | 1 pc | 1512540142 | A | |
| 160 mm | 1 pc | 1516040182 | A | |
| 200 mm | 1 pc | 1520060202 | A | |
| 250 mm | 1 pc | 1525015302 | A | |
| 315 mm | 1 pc | 1531515302 | A | |
| 355 mm | 1 pc | 1535515302 | A | |
| 400 mm | 1 pc | 1540015302 | A | |
| 500 mm | 1 pc | 1550015302 | A |
Application
INTU FR COLLAR (ST) is a pipe closure element used for fireproof sealing of single service penetrations of metal and combustible pipes, either individually or in bundles, passing through walls or floors.
Flexible wallsThe wall should be at least 100 mm thickness (constructed with a minimum of two plasterboards lining both sides).
Rigid wallsThe wall should be at least 100 mm thickness (made of concrete or masonry with a density of not less than 600 kg/m3).
Rigid floorThe floor should be at least 150 mm thickness (made of concrete, reinforced concrete, cellular concrete, with a density of not less than 1700 kg/m3).
Transport and storage
Transport and store in a dry and cool place at a temperature of + 5°C to + 35°C.
-
24 years of industry experience
-
Proven effectiveness backed by reports
-
Tested and certified solutions
-
Global distribution network