Product description

The INTU FR COLLAR consists of one or more layers of intumescent graphite-based inserts, each with a nominal thickness of 2.0 mm, enclosed in a steel sheet housing coated with red, corrosion-resistant paint. The collar is fitted with a locking clasp to secure its ends and keep it stable on the pipe, as well as mounting brackets for fixing it to the wall or floor.

The INTU FR COLLAR is available in a red housing version – INTU FR COLLAR – and in a stainless steel housing version – INTU FR COLLAR (ST). Both collars are the same product with very high fire protection parameters – in a fire, the collar creates a barrier, ensuring the partition maintains its tightness and insulation up to EI 240.

  • Fire resistance class up to EI 240

  • Combustible pipes fire protection

  • For walls and floors

  • Quick installation

  • High degree of swelling

  • Certification LEED & BREEAM

Compliance

  • European Technical Assessment: ETA-19/0844
  • Declaration of Performance: DoP 2/2019
  • Certificate of Constancy of Performance: 1488-CPR-0825/W
  • VOC Emission test report – Indoor Air Comfort GOLD
  • Certification LEED & BREEAM

Availability

ProductTypeDelivery formArticle numberDelivery group
INTU FR COLLAR32 mm1 pc1503230040A
40 mm1 pc1504030040A
55 mm1 pc1505530060A
63 mm1 pc1506330060A
75 mm1 pc1507530060A
82 mm1 pc1508230080A
90 mm1 pc1509030080A
110 mm1 pc1511030100A
125 mm1 pc1512540140A
160 mm1 pc1516040180A
200 mm1 pc1520060200A
250 mm1 pc1525015300A
315 mm1 pc1531515300A
fire

Application

INTU FR COLLAR is a pipe closure element used for fireproof sealing of single installation penetrations of metal and combustible pipes, either individually or in bundles, passing through walls or floors.

Flexible walls

The wall should be at least 100 mm thickness (constructed with a minimum of two plasterboards lining both sides).

Rigid walls

The wall should be at least 100 mm thickness (made of concrete or masonry units with a density of not less than 600 kg/m3).

Rigid floor

The floor should be at least 150 mm thickness (made of concret fore example: reinforced concrete, cellular concrete, with a density of not less than 1700 kg/m3).

Transport and storage

Transport and store in a dry and cool place