INTU FR COLLAR L SLIM

INTU FR COLLAR L SLIM

Fire protection collar in roll

Product description

INTU FR COLLAR L SLIM consists of at least two layers of graphite-based intumescent material, each with a nominal thickness of 2.0 mm and a width of 30 mm, enclosed in a 0.5 mm stainless steel casing. The casing is equipped with mounting brackets for securing the collar to the partition.

  • Fire resistance class up to EI 240

  • Protection of combustible pipes

  • For use in walls and ceilings

  • Quick installation and sealing of hard-to-reach passages

  • High degree of swelling

Compliance

  • European Technical Assessment:
    ETA-24/0497
  • Declaration of performance:
    DoP 2/2024

Availability

ProductTypeDelivery formArticle numberDelivery group
INTU FR COLLAR L SLIMContents of set: Steel casing 2.52m, Intumescent filling 12m, Short mounting bracket “S”1 pc1603005250A
Short fastening clamp “S”1 set – 20 pcs.1610200000A
Long “L” mounting bracket1 set – 20 pcs.1620200000A
fire

Application

INTU FR COLLAR L SLIM is a universal collar used for sealing installation penetrations of pipes, cables, and cable ducts, single or in bundles, passing through walls and ceilings.

Flexible walls

The wall should be at least 100 mm thick. It should be made with a facing of at least two plasterboards on both sides (total facing thickness on one side of the wall not less than 25 mm).

Rigid walls

The wall should be at least 100 mm thick. It should be made of concrete or masonry units with a density of not less than 450 kg/m3.

Rigid ceiling

The ceiling should be at least 150 mm thick. It should be made of concrete, reinforced concrete, cellular concrete, with a density of not less than 550 kg/m3.

Transport and storage

Transport and store in a dry and cool place
at a temperature of + 5°C to + 35°C.