INTU FR COLLAR L SLIM
Fire protection collar in roll
Product description
INTU FR COLLAR L SLIM consists of at least two layers of graphite-based intumescent material, each with a nominal thickness of 2.0 mm and a width of 30 mm, enclosed in a 0.5 mm stainless steel casing. The casing is equipped with mounting brackets for securing the collar to the partition.
-
Fire resistance class up to EI 240
-
Protection of combustible pipes
-
For use in walls and ceilings
-
Quick installation and sealing of hard-to-reach passages
-
High degree of swelling
Documentation
Compliance
- European Technical Assessment:
ETA-24/0497 - Declaration of performance:
DoP 2/2024
Availability
Product | Type | Delivery form | Article number | Delivery group |
INTU FR COLLAR L SLIM | Contents of set: Steel casing 2.52m, Intumescent filling 12m, Short mounting bracket “S” | 1 pc | 1603005250 | A |
Short fastening clamp “S” | 1 set – 20 pcs. | 1610200000 | A | |
Long “L” mounting bracket | 1 set – 20 pcs. | 1620200000 | A |

Application
INTU FR COLLAR L SLIM is a universal collar used for sealing installation penetrations of pipes, cables, and cable ducts, single or in bundles, passing through walls and ceilings.
Flexible wallsThe wall should be at least 100 mm thick. It should be made with a facing of at least two plasterboards on both sides (total facing thickness on one side of the wall not less than 25 mm).
Rigid wallsThe wall should be at least 100 mm thick. It should be made of concrete or masonry units with a density of not less than 450 kg/m3.
Rigid ceilingThe ceiling should be at least 150 mm thick. It should be made of concrete, reinforced concrete, cellular concrete, with a density of not less than 550 kg/m3.
Transport and storage
Transport and store in a dry and cool place
at a temperature of + 5°C to + 35°C.
-