Product description

INTU FR WRAP L is a fire protection tape made from a graphite-based intumescent material that expands when exposed to high temperatures. In the event of a fire, it swells to form a barrier that prevents the spread of flames and smoke, maintaining the partition’s integrity and insulation for up to EI 240.

  • Fire resistance class up to EI 240

  • Protection of combustible pipes

  • For use in walls and ceilings

  • Quick installation and sealing of hard-to-reach passages

  • High degree of swelling

Compliance

  • European Technical Assessment:
    ETA-18/0593
  • Declaration of Performance:
    DoP 11/2019
  • Classification:
    01988.2/23/Z00NZP
  • Certificate of Constancy of Performance:
    1488-CPR-0722/W

Availability

ProductTypeDelivery formArticle numberDelivery group
INTU FR WRAP L60 mm x 10 mb1 pc1006010000A
60 mm x 10 mb (TS)1 pc1006010001A
60 mm x 25 mb 1 pc1006025000A
60 mm x 25 mb (TS)1 pc1006025001A
100 mm x 10 mb 1 pc1010010000A
100 mm x 10 mb (TS)1 pc1010010001A
100 mm x 25 mb 1 pc1010025000A
100 mm x 25 mb (TS)1 pc1010025001A
fire

Application

INTU FR WRAP L tape is used for fire protection of plastic, composite, and multilayer composite pipes passing through fire-separating partitions, either individually or in bundles, as well as combustible and non-combustible pipes with insulation.

Flexible walls

The wall should be at least 125 mm thick. It should be constructed with a cladding of at least two plasterboards on both sides

Rigid walls

The wall should be at least 125 mm thick. It should be made of concrete or masonry units with a density of not less than 600 kg/m3.

Rigid ceiling

The ceiling should be at least 150 mm thick. It should be made of concrete (reinforced, cellular, masonry) with a density of not less than 1700 kg/3.

Transport and storage

Transport and store in a dry and cool place at a temperature of + 5°C to + 35°C.

  • 24 years of industry experience

  • Proven effectiveness backed by reports

  • Tested and certified solutions

  • Global distribution network