INTU FR WRAP
Fire protection band
Product description
INTU FR WRAP fire protection ties are made from a graphite-based material that swells during a fire to prevent the spread of fire, creating a barrier that ensures the partition remains airtight and insulating up to EI 240.
-
Fire resistance class up to EI 240
-
Protection of combustible pipes
-
For use in walls and ceilings
-
Quick installation and sealing of hard-to-reach passages
-
High degree of swelling
Documentation
Compliance
- European Technical Assessment:
ETA-18/0593 - Declaration of Performance:
DoP 1/2019 - Certificate of Constancy of Performance:
1488-CPR-0722/W
Availability
Product | Type | Delivery form | Article number | Delivery Group |
INTU FR WRAP | 32 mm | 1 pc | 1203206010 | A |
40 mm | 1 pc | 1204006010 | A | |
55 mm | 1 pc | 1205506010 | A | |
63 mm | 1 pc | 1206306010 | A | |
75 mm | 1 pc | 1207506010 | A | |
82 mm | 1 pc | 1208206020 | A | |
110 mm | 1 pc | 1211006020 | A | |
125 mm | 1 pc | 1212510040 | A | |
160 mm | 1 pc | 1216010050 | A | |
200 mm | 1 pc | 1220010080 | A |

Application
The INTU FR WRAP clamp is used for fire protection of plastic, composite and multilayer composite pipes passing through fire separation divisions individually or in bundles, as well as combustible and non-combustible pipes in insulation.
Flexible wallsThe wall should be at least 100 mm thick. It should be constructed with a minimum of two plasterboards lining both sides.
Rigid wallsThe wall should be at least 100 mm thick. It should be made of concrete or masonry units with a density of not less than 450 kg/m3.
Rigid ceilingThe ceiling should be at least 150 mm thick. It should be made of concrete, reinforced concrete, cellular concrete, with a density of not less than 550 kg/m3.
Transport and storage
Transport and store in a dry and cool place
at a temperature of + 5°C to + 35°C.
-
24 years of industry experience
-
Proven effectiveness backed by reports
-
Tested and certified solutions
-
Global distribution network